UMG 604-PRO

Technical details

Item no.: see product variants
Janitza UMG 604-PRO Front

Data at a glance

Harmonics V / A

1st – 40th

Active energy class

0.5S (…/5 A)

Digital inputs

2

Digital / Pulse output

2

Memory size

128 MB

Interfaces

  • RS232
  • RS485
  • Ethernet

Protocols

  • Modbus RTU
  • Modbus Gateway
  • Modbus RTU over Ethernet
  • SNMP
  • BACnet IP (optional)
  • Modbus TCP/IP

Product variants

Item no.: 5216202

Certifications

  • ul

Supply voltage AC

95 … 240 V AC

Supply voltage DC

135 … 340 V DC

Item no.: 5216012

Supply voltage AC

50 … 110 V AC

Supply voltage DC

50 … 155 V DC

Item no.: 5216222

Certifications

  • ul

Supply voltage AC

20 … 50 V AC

Supply voltage DC

20 … 70 V DC

Functions and features

Large measurement data memory

  • 128 MByte
  • 5.000.000 saved values
  • Recording range up to 2 years
  • Recording freely configurable

Graphical programming

  • Comprehensive programming options on the device, 7 programs simultaneously (PLC functionality)
  • Jasic® source code programming
  • Functional expansions far beyond pure measurement
  • Complete APPs from the Janitza library

Ethernet-Modbus-gateway and high-speed-Modbus

  • Simple integration of Modbus-RTU devices into an Ethernet architecture through the Modbus gateway function
  • Integration of devices with identical file formats and matching function codes possible via Modbus RTU interface
  • Fast and reliable data exchange via RS485 interface
  • Speed up to 921.6 kB/s

Modern communications architecture via Ethernet

  • Rapid, cost-optimised and reliable communication through integration into an existing Ethernet architecture
  • Integration in PLC systems and building management systems
  • High flexibility due to the use of open standards
  • Simultaneous polling of interfaces possible

DIN mounting rail (6TE): Simple and cost-optimised installation

  • Mounting on a 35 mm DIN rail
  • Clear cost advantages in the switch cabinet construction through lower installation and connection effort
  • Simple integration into the LVDB, in machinery construction, in installation subdistribution panel for building management systems, in IT and in data centres

Power quality

  • Harmonics analysis up to 40th harmonic
  • Unbalance
  • Distortion factor THD-U /THD-I
  • Measurement of positive, negative and zero sequence component
  • Short-term interruptions (> 20 ms)
  • Logging and storage of transients (> 50 μs)
  • Start-up processes
  • Fault recorder function
  • Rotary field indication