Technical details
Item no.: see product variants
Data at a glance
Harmonics V / A
1st – 63rdActive energy class
0.5S (…/5 A)Digital inputs
2Digital / Pulse output
2Memory size
128 MBInterfaces
- RS232
- RS485
- D-Sub-9 connector (Profibus)
- Ethernet
Protocols
- Modbus RTU
- Modbus Gateway
- Profibus DP V0
- Modbus RTU over Ethernet
- SNMP
- BACnet IP (optional)
- Modbus TCP/IP
Product variants
Item no.: 5216227
Certifications
- ul
Supply voltage AC
95 … 240 V ACSupply voltage DC
135 … 340 V DCItem no.: 5216028
Supply voltage AC
50 … 110 V ACSupply voltage DC
50 … 155 V DCItem no.: 5216229
Certifications
- ul
Supply voltage AC
20 … 55 V ACSupply voltage DC
20 … 77 V DCFunctions and features
Power quality
- Continuous power quality monitoring (e.g. EN 50160)
- Harmonics analysis up to the 63rd harmonic, even and odd
- Interharmonics
- Distortion factorTHD-U /THD-I
- Measurement of positive, negative and zero sequence component
- Flicker measurement in accordance with DIN EN 61000-4-15
- Logging and storage of transients (> 50 μs)
- Recording of short-term interruptions (> 20 ms)
- Monitoring start-up processes
- Recorder for limit value events
Power
- 4 voltage and 4 current measurement inputs
- Logging and digitalisation of effective values (true RMS) of currents and voltages (15 – 440 Hz)
- Continuous sampling of the voltage and current measurement inputs at 20 kHz
- Recording of over 2,000 measured values per measurement cycle (200 ms)
- Stipulation of nominal current possible for measuring current events
- Fourth current measurement input is suitable for measuring the current in the neutral or PE conductor or for measuring any potential difference between N and PE
- Large measured data memory (memory range = 5 000 000 measured values)
- Simple remote polling of measured data via the device's own homepage
- All interfaces can be used simultaneously
- Up to 4 ports can be accessed simultaneously
Impressive reporting with GridVis®
- Automatic generation and sending of power quality reports
- Power quality reports per EN 50160, EN 61000-2-4, IEEE519
- Illustration of the ITI-(CBEMA) curve
- Freely definable time planning for the generation of reports
Modern communications architecture via Ethernet
- Rapid, cost-optimised and reliable communication through integration into an existing Ethernet architecture
- Integration in PLC systems and building management systems
- High flexibility due to the use of open standards
- Simultaneous polling of interfaces possible
Convenient home page and email functions
Information can be received conveniently by email and via the device homepage
Access to powerful device homepage via web browser
Online data, historical data, graphs, events and much more, is available direct from the homepage
Graphical programming
- Comprehensive programming options on the device, 7 programs simultaneously (PLC functionality)
- Jasic® source code programming
- Functional expansions far beyond pure measurement
- Complete APPs from the Janitza library
Ethernet-Modbus gateway and high-speed-Modbus
- Simple integration of Modbus-RTU devices into an Ethernet architecture through the Modbus gateway function
- Integration of devices with identical file formats and matching function codes possible via Modbus RTU interface
- Fast and reliable data exchange via RS485 interface
- Speed up to 921.6 kB/s
Large measurement data memory
- 128 MByte
- 5.000.000 saved values
- Recording range up to 2 years
- Recording freely configurable by the user