UMG 96-PQ-L

Technical details

Item no.: see product variants
Janitza UMG 96-PQ-L Front 2
Janitza UMG 96-PQ-L Front 1
Janitza UMG 96-PQ-L Front EN 2
Janitza UMG 96-PQ-L Front EN 4
Janitza UMG 96-PQ-L Front EN 5

Data at a glance

Certifications

  • UL certified

Harmonics V / A

1st – 65th

Active energy class

0.2S (…/5 A)

Digital inputs

3

Digital / Pulse output

3

Memory size

64 MB

Interfaces

  • RS485

Protocols

  • Modbus RTU

Networks

  • TT-Net
  • TN-Net

Product variants

Item no.: 5236001

Supply voltage AC

90 … 277 V AC

Supply voltage DC

90 … 250 V DC

IEC 61000-4-30

Class S - activatable

Item no.: 5236002

Supply voltage AC

24 … 90 V AC

Supply voltage DC

24 … 90 V DC

IEC 61000-4-30

Class S - activatable

Item no.: 5236005

Supply voltage AC

90 … 277 V AC

Supply voltage DC

90 … 250 V DC

IEC 61000-4-30

Class S - activatable

Networks

  • IT-Net

Item no.: 5236021

Supply voltage AC

90 … 277 V AC

Supply voltage DC

90 … 250 V DC

IEC 61000-4-30

Class S

Item no.: 5236022

Supply voltage AC

24 … 90 V AC

Supply voltage DC

24 … 90 V DC

IEC 61000-4-30

Class S

Item no.: 5236025

Supply voltage AC

90 … 277 V AC

Supply voltage DC

90 … 250 V DC

IEC 61000-4-30

Class S

Networks

  • IT-Net

Functions and features

Power quality

  • Harmonics current up to the 65th harmonic
  • High sampling rate with 280 sampling points per full wave
  • 1 ms digital input event capture rate
  • 20 ms RMS value memory
  • Full-wave events

Visualization

  • Función de osciloscopio
  • Diagrama fasorial en la pantalla
  • Historia de los indicadores de seguimiento en la pantalla
  • Restablecimiento de los indicadores de seguimiento a través de la pantalla o remotamente

Installation & Integration

  • Overvoltage category 600 V CAT III
  • Easy installation thanks to 96 x 96 mm front panel
  • Use in IT networks with variants 52.36.005
  • Time setting via third-party systems according to DIN 60970-5-4

Energy management

  • Identify savings potentials
  • Active energy class 0.2S#
  • Compliance with regulatory and tax requirements
  • Configurable screened average value

Memory

  • High memory depth with low memory requirements
  • Storage depth up to 15 years with 23 measured values of 15 min. each and 8 measured values of 1 h each
  • Memory partitioning into long-term memory and high-resolution PQ shortterm memory

Modularity

  • Temperature measurement with monitoring via integrated comparator
  • Ethernet interface and Modbus gateway
  • Multifunction inputs for residual current measurement or DC power measurement
  • Neutral conductor measurement (I4 – current measurement)

Peripherals

  • 3 digital outputs
  • 1 analog output
  • 3 digital inputs

Operation

  • 6-button operation on the color graphic display
  • Intuitive operation
  • Configuration directly on the display
  • On-site and remote operation with GridVis®
  • Configurable home screen and jump-back point

Comparator

  • 50 comparators in the device
  • Hysteresis
  • Predefined comparator profiles for quick configuration (GridVis®)

Class S

  • Flicker
  • Interharmonics
  • Standard-compliant PQ data based on, e.g. EN 50160 and IEEE519
  • Rapid voltage change
  • Overfrequencies & underfrequencies
  • Predefined recording profiles for EN 50160, IEEE519,61000-2-4, AHF and SVG

Events

  • Representation in the display
  • Read out last event via Modbus
  • Display root-mean-square value curves in the GridVis® event browser

Communication

  • Modbus Client/Server gateway functionality
  • Gateway function
  • Ethernet interface
  • RS485
  • 5 simultaneous Modbus TCP connections