Ficha técnica
Nº de artículo: ver variantes de productos
Los datos de un vistazo
Certificaciones
- Certificado UL
Armónicos V / A
1. – 65.Clase de energía activa
Clase 0,5S (… A/333 mV) y 0,5S para las bobinas Rogowski (... mV/kA)Entradas digitales
3Salida digital / de pulsos
3Tamaño de memoria
64 MBInterfaces
- RS485
Protocolos
- Modbus RTU
Redes
- Red TT
- Red TN
Variantes del producto
Nº de artículo: 5236006
Tensión de alimentación CA
90 … 277 V ACTensión de alimentación CC
90 … 250 V DCNº de artículo: 5236007
Tensión de alimentación CA
24 … 90 V ACTensión de alimentación CC
24 … 90 V DCFunciones y características
Power quality
- Harmonics current up to the 65th harmonic
- High sampling rate with 280 sampling points per full wave
- 20 ms RMS value memory for full-wave events
Energy management
- Identify savings potentials
- Active energy class 0.5 S
- Compliance with regulatory and tax requirements Configurable screened average values
Visualization
- Oscilloscope function
- Phasor diagram on the display
- History of drag indicator values on the display
- Resetting of the drag indicator values via display or remotely
Operation
- 6-button operation on the color graphic display
- Intuitive operation
- Configuration directly on the display
- On-site operation
- Configurable home screen and jump-back point
Events
- Representation in the display
- Read out last event via Modbus
- Display root-mean-square value curves in the GridVis® event browser
Modularity
- Temperature measurement with monitoring via integrated comparator
- Ethernet interface and Modbus gateway
- Multifunction inputs for residual current measurement or DC power measurement
Limit value monitoring
- 50 comparators in the device
- Hysteresis
- Predefined comparator profiles for quick configuration (GridVis®)
Peripherals
- 3 digital outputs
- 1 analog output
- 3 digital inputs
- 4 power inputs directly from the basic device
Installation & integration
- Overvoltage category 600 V CAT III / 300 V CAT IV
- Easy installation thanks to 96 x 96 mm front panel
- Time setting via third-party systems according to EN 60870-5-4:1993
- Serial interface with Modbus RTU
Communication
- Client / Server*
- Gateway function*
- Ethernet interface*
- RS-485
- 5 simultaneous Modbus TCP connections*
*with module 96-PA-RCM-EL
Memory
- High memory depth with low memory requirements
- Memory depth up to 15 years with 23 measured values of 15 min each and 8 measured values of 1 h each
- Memory partitioning into long-term memory and high-resolution PQ short-term memory