Rogowski coils without connectors for the UMG 96-PQ L-LP
Janitza Low Power Wandler

The Rogowski coil is used to measure the current of AC currents and is primarily used for particularly simple retrofitting in existing systems - either around busbars or around power cables. The output signal of a Rogowski coil differs from that of conventional current transformers. This must be taken into account when connecting. Janitza offers Rogowski coils that are used in conjunction with a measuring transducer as well as Rogowski coils that are suitable for direct connection to corresponding measuring devices.

Contact us

Basic data for Rogowski current transformer

  • Frequency bandwidth of the Rogowski coil 50/60 Hz, up to 700 kHz in idle mode (without load)
  • Accuracy to class 0.5, according to IEC 61869
  • Operating temperature: -40°C to +80°C
  • Rated insulation voltage 1 kV CAT III
  • Rogowski coil from 10 to 10000 A RMS – in combination with Janitza measurement transducer RogoTrans up to 4000 A RMS
  • Accuracy better than 0.65% regardless of the position of the primary conductor
  • Sealing possible
  • CE certified (2014/30/EU), in accordance with the European Directive 2014/35/EU and tested in accordance with the IEC 61010-1 standard
  • Unique, IP67, flexible and precise AC current transformer with separable core, based on Rogowski coil technology
  • Subsequent clip-on without disconnecting the conductor
  • Device for fixing to the primary conductor with a cable tie
  • Internal shielding
  • High linearity, no saturation, no upper current limit of the Rogowski coil

Rogowski-Spule-Messumformer
Measurement transducer for Rogowski current transformer

Basic data for measurement transducers

The measurement transducer for the Rogowski current transformer RogoTrans measures alternating currents and has a standardized output signal of 0...1 A. The measuring range extends up to 4000 A, the power supply is 24 V DC. The design of the measurement transducer is very compact and can be mounted on a DIN rail.

  • Measurement transducer for Rogowski current transformer (Part no. 15.03.609, 15.03.610, 15.03.611)
  • Standardized output signal 0 ... 1 A
  • For measuring alternating currents
  • Measuring range up to 4000 A
  • Power supply: 24 VDC
  • Compact design in plastic housing
  • DIN rail mounting possible

Get in touch

Get personal advice now

Your request is important to us and we guarantee fast and professional processing.